Airflow and height estimator
Two quick estimates from figures you enter: how much air has to pass through to carry a heat load away, and how much rack space a chassis gives before you subtract what sits under the cooler. Nothing you type leaves this page.
How the estimates work
Airflow needed
airflow (m³/s) = heat (W) ÷ (ρ × cp × ΔT)
CFM = m³/s × 60 ÷ 0.028316846592 ≈ 1.76 × W ÷ ΔT (°C) - ρ = 1.2 kg/m³ and cp = 1005 J/(kg·K): the density of dry air and its specific heat at constant pressure, at the usual room-temperature, sea-level convention (101.325 kPa). The sensible heat balance is heat = mass flow × cp × ΔT, and mass flow = ρ × volume flow.
- ΔT is how much warmer the air leaves than it arrives. One °C of rise is one K. A rise entered in °F is converted with × 5/9 (a difference, so no 32 offset).
- Unit conversions: 1 ft = 0.3048 m exactly, so 1 ft³ = 0.028316846592 m³ and 1 m³/s ≈ 2118.88 CFM (a rounded figure). One minute is 60 s, one hour is 3600 s and 1 L = 0.001 m³.
- It assumes all the heat goes into the air stream and the air is evenly mixed. Thinner air at altitude carries less heat per cubic metre, so it needs more volume than this.
- The result is bulk airflow through the air path that carries the heat you entered. If you enter whole-server heat, it is the air for the whole server, not only the air that crosses the heatsink fins. Installed fan flow depends on the fan curve and the resistance of the system (fins, filters, drive cages), so a fan's free-air rating is not what you will get.
Height envelope
estimated room (mm) = U × 44.45 mm − total space lost
inches = mm ÷ 25.4 - 1U = 1.75 in = 44.45 mm, the rack unit of the EIA-310 rack standard; 1 in = 25.4 mm exactly.
- That is the rack space, not the chassis. A real 1U chassis is usually a little under 44.45 mm tall so units do not rub. Total space lost is everything you subtract: the chassis floor and lid, the mounting stack (standoffs, board, socket), and any obstruction above or below the cooler.
- The comparison with a cooler height is plain subtraction. Use the chassis maker's stated CPU cooler clearance when there is one; it already includes what this estimate cannot see, such as a crossbar or a power supply over the socket.
Both results are estimates for planning, not a fit or cooling guarantee. For the height limits common in 2U, 3U and 4U chassis, see the guides.
Sources for the constants
- ASHRAE Handbook: Fundamentals, chapter 18, Nonresidential Cooling and Heating Load Calculations, ASHRAE (1.20 kg/m³, 1005 J/(kg·K) and the sea-level pressure convention)
- ASHRAE Handbook: HVAC Systems and Equipment, chapter 13, Hydronic Heating and Cooling, ASHRAE (equation 1, the sensible heat balance)
- Straightening Out Fan Curves, Air Movement and Control Association (AMCA) (installed fan flow depends on the fan curve and system resistance)
- NIST Guide to the SI, Appendix B.9, National Institute of Standards and Technology (inch, foot and temperature-interval conversion factors)
- NIST Guide to the SI, Chapter 5: Units Outside the SI, National Institute of Standards and Technology (60 s per minute, 3600 s per hour, 1 L = 0.001 m³)
- Announcement Letter - 9306 Rack Enclosure, IBM (EIA-310-D rack unit of 1.75 in, 44.45 mm)